Inspection Information:
Facility Type: | WS3 |
Inspection type: | Routine |
Inspection date: | October 23, 2006 |
Number of critical violations: | 1 |
Number of non-critical violations: | 1 |
Follow-up Required: | No |
This facility was given a moderate hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description |
317 | Critical Inadequate or improper construction of water works Observation: Well casing is located in a well pit. Well casing was extended, however the well pit was not filled. There is a pipe located near the bottom of the well pit suggesting that this area periodically becomes flooded with surface water. Corrective Action: The area where the well is located is subject to storm water run-off during heavy rainfalls and spring melt, which could carry contaminated surface water towards the well and collect in the well pit. Contaminated surface water could potentially enter the well by flowing down the outside of the casing. The well pit is to be filled in and the well is to be sealed with a surface seal (as outlined in the BC Groundwater Protection Regulation). The soil at grade is to be sloped up to the well casing to prevent the ponding of water around the wellhead. |
318 | Inadequate Microbiological Analysis data Observation: There is no record of bacteriological sample results in the last year for this water system. Corrective Action: As per Operating Permit Condition, bacteriological sampling is required at least quarterly. Ensure that this sampling frequency is met. Sample collected on October 24 by Jeff Kresowaty (EHO). Next sample is due in January 2007. |