Inspection Information:
Facility Type: | WS3 |
Inspection type: | Initial |
Inspection date: | February 24, 2011 |
Number of critical violations: | 0 |
Number of non-critical violations: | 1 |
Follow-up Required: | No |
This facility was given a moderate hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description |
313 | Inadequate treatment Observation: No chlorine found in distribution system. Dorm B washroom = 0.01 ppm. Well room main reservoir = 0.01 ppm. System last tested at 0.64 ppm Dorm C washroom. Corrective Action: Please ensure water system has free chlorine residual of 0.2 ppm minimum. Please ensure system is maintained. |