Inspection Information:
Facility Type: | WS4 |
Inspection type: | Routine |
Inspection date: | April 21, 2008 |
Number of critical violations: | 0 |
Number of non-critical violations: | 3 |
Follow-up Required: | No |
This facility was given a moderate hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description |
317 | Inadequate or improper construction of water works Observation: Grade is not mounded up to well to casing. Slope impermeable soil away from well to prevent contaminated surface water from reaching the well casing and infiltrating the well Corrective Action: a shed will be constructed over the well |
319 | Inadequate Chemical Analysis Data Observation: require full chemical analysis as soon as possible Corrective Action: (no corrective action) |
320 | Other (specify below) Observation: well log; system schematic and water treatment equipment specifications required as soon as possible Corrective Action: (no corrective action) |