PHYSICAL FACILITY, EQUIPMENT AND FURNISHINGS: 31100 - RCR s.17 - A licensee must ensure that water accessible to a person in care, from any source, is not heated to more than 49° Celsius.
Observation: The water temperature was sampled throughout the facility, and in all areas the temperature exceeded 49 degrees. Temps were noted to be between 51-66 degrees.
Corrective Action(s): Ensure water accessible to persons in care, is not heated to more than 49 degrees Celsius.
Date to be Corrected: March 4, 2022
PHYSICAL FACILITY, EQUIPMENT AND FURNISHINGS: 31760 - RCR s.35(1)(c) - A licensee must provide the following appropriately furnished and equipped areas: (c) secure, safe and adequate storage areas for cleaning agents, chemical products and other hazardous materials.
Observation (CORRECTED DURING INSPECTION): It was observed in 3 or more kitchenette areas, accessible to persons in care, that there were chemicals stored under the sink, and the lock was either not working or not engaged.
Corrective Action(s): Immediate action was taken, and locks were replaced and engaged by the end of the inspection, securing the items under the sinks.
Date to be Corrected: corrected
|