Van Anda Improvement Dist. Water System - Inspection Report

Inspection Information:

Facility Type:  WS2
Inspection type:  Routine
Inspection date:  December 08, 2009
Follow-up Required:  No

This facility was given a moderate hazard rating.
More information on hazard ratings.

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
304  Critical Inadequate Water Quality / Disinfection / Treatment / Quantity
Observation: 25 Inadequate treatment for the removal of parasitic cysts of Giardia / Cryptosporidium
Corrective Action: Water is currently not treated for removal/inactivation of parasytic cysts. VAID should begin sampling program to help assess options available for meeting this requirement.
304  Critical Inadequate Water Quality / Disinfection / Treatment / Quantity
Observation: 35 Inadequate treatment to reduce organics (i.e. nitrates, hydrogen sulphide)
Corrective Action: High levels of organics in source water result in the formation of higher than desirable levels of disinfection by-products (THMs and HAAs)

Comments:
None