Inspection Information:
Facility Type: | WS2 |
Inspection type: | Routine |
Inspection date: | March 15, 2007 |
Follow-up Required: | Yes |
This facility was given a low hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
304 | Critical Inadequate Water Quality / Disinfection / Treatment / Quantity Observation: 25 Inadequate treatment for the removal of parasitic cysts of Giardia / Cryptosporidium Corrective Action: Water treatment remains only chlorination. Consulting engineering report is underway to assist operators in determining appropriate options for providing treatment to the 4,3,3,<1 treatment standard. |
304 | Critical Inadequate Water Quality / Disinfection / Treatment / Quantity Observation: 40 Inadequate treatment to reduce turbidity from silt and organics Corrective Action: Water exhibits relatively high total organic carbon and turbidity levels at times. This complicates the ability to treat to the required level and must also be addressed as it results in THM levels which exceed the standard of 100 ppb. |
309 | Inadequate Emergency Response Plan / Implementation Observation: 10 Emergency Response Plan has not been updated to include additional hazards / revised contact lists / etc. Corrective Action: Ensure Emergency Response plan is reviewed and contact information is updated. |
Comments:
None