Inspection Information:
Facility Type: | WS2 |
Inspection type: | Annual Report |
Inspection date: | March 30, 2012 |
Follow-up Required: | No |
This facility was given a moderate hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
304 | Critical Inadequate Water Quality / Disinfection / Treatment / Quantity Observation: 17 Water sample positive for fecal coliform Corrective Action: Out of a total of 302 treated water samples submitted in 2011, 35 had total coliforms detected and 2 had e. coli bacteria detected. This exceeds the maximum acceptable standard. |
304 | Critical Inadequate Water Quality / Disinfection / Treatment / Quantity Observation: 25 Inadequate treatment for the removal of parasitic cysts of Giardia / Cryptosporidium Corrective Action: This surface water source is only disinfected with chlorine at present, and is therefore not capable of removing or inactivating Giardia and Cryptosporidium. |
304 | Critical Inadequate Water Quality / Disinfection / Treatment / Quantity Observation: 40 Inadequate treatment to reduce turbidity from silt and organics Corrective Action: High levels of organics in the source water result in a high chlorine demand and elevated levels of disinfection byproducts in the finished water. |
Actions Taken:
Issue Boil Advisory
As a result of unacceptable treated water quality there were 2 Boil Advisories issued in 2011 for a total of 61 days.
Comments:
None