Inspection Information:
Facility Type: | WS3 |
Inspection type: | Routine |
Inspection date: | September 24, 2012 |
Follow-up Required: | No |
This facility was given a moderate hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
501 | Critical Failure to disinfect surface water Observation: Failure to provide 3 log reduction for protozoa. Corrective Action: Water is only treated with chlorination at present. A 2nd level of treatment is required for all GUDI and surface water sources. Evaluate options and submit compliance plan with timelines to satisfy VCH treatment expectations. |
Comments:
None