Texada Quarry (A Div. of Lafarge) - Main Water System - Inspection Report

Inspection Information:

Facility Type:  WS3
Inspection type:  Follow-Up
Inspection date:  August 10, 2015
Follow-up Required:  No

This facility was given a low hazard rating.
More information on hazard ratings.

Violations:
No violations were found during the inspection

Comments:
Reinspection of water treatment and distribution system carried out following servicing of treatment works. Free available chlorine level in storage tank was measured to be at 1.0 mg/L; free available chlorine level at last tap was 0.37 mg/L. This is despite 20.0 mg/L reading on injection pump. Unclear if this is accurate, although calibration has been done. UV system operational and bypass valve handle has been removed. 1 bacteriological water sample collected during inspection. Recent full chemical water sample submitted but results not yet received.