Inspection Information:
Facility Type: | WS3 |
Inspection type: | Routine |
Inspection date: | February 24, 2009 |
Follow-up Required: | Yes |
This facility was given a high hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
304 | Critical Inadequate Water Quality / Disinfection / Treatment / Quantity Observation: 25 Inadequate treatment for the removal of parasitic cysts of Giardia / Cryptosporidium Corrective Action: Well is shallow and under surface influence. No treatment in place for removal/inactivation of giardia and cryptosporidium. |
304 | Critical Inadequate Water Quality / Disinfection / Treatment / Quantity Observation: 17 Water sample positive for fecal coliform Corrective Action: Issues with operation of disinfection system resulted in over 45% of samples submitted in 2008 showing presence of e. coli and/or total coliform bacteria. a Boil Water Advisory was instituted and remains in place at this time. |
310 | Other (Specify) Observation: 05 Non-compliance with the conditions of the Operating Permit Corrective Action: The Construction Permit process has not been completed and a CP has not been issued yet for completed works. |
Actions Taken:
Issue Boil Advisory
Boil Water Advisory remains in place.
Comments:
None