Inspection Information:
Facility Type: | WS3 |
Inspection type: | Routine |
Inspection date: | November 13, 2013 |
Follow-up Required: | No |
This facility was given a high hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
104 | Critical Failure to flood proof a well in accordance with the Regulation Observation: Well is susceptible to runoff water and would be vulnerable to flood water. Corrective Action: Feasibility study has been approved to proceed and should provide options for delivering safe drinking water. |
401 | Critical Failure to provide potable water Observation: Water treatment system is not capable of delivering potable water consistently. Corrective Action: |
409 | Total coliform exceedance Observation: 3 of 16 samples submitted to date in 2013 were positive for total coliforms. Corrective Action: Feasibility study is intended to provide direction in this regard. |
410 | Critical Water sample positive for E. Coli Observation: 2 samples submitted in 2013 to date were positive for e. coli bacteria. Corrective Action: Boil Water Advisory remains in place. |
Comments: