Inspection Information:
Facility Type: | WS2 |
Inspection type: | Routine |
Inspection date: | December 08, 2009 |
Follow-up Required: | No |
This facility was given a moderate hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
304 | Critical Inadequate Water Quality / Disinfection / Treatment / Quantity Observation: 16 Water sample positive for total coliform Corrective Action: Approximately 20% of finished water samples since April 2009 were positive for total coliforms. Continue adjusting chlorination system to ensure adequate water disinfection occurs on an ongoing basis. |
304 | Critical Inadequate Water Quality / Disinfection / Treatment / Quantity Observation: 25 Inadequate treatment for the removal of parasitic cysts of Giardia / Cryptosporidium Corrective Action: Water is not currently treated for removal/inactivation of parasytic cysts. Sand filter project underway needs to be completed and recommendations provided. |
304 | Critical Inadequate Water Quality / Disinfection / Treatment / Quantity Observation: 35 Inadequate treatment to reduce organics (i.e. nitrates, hydrogen sulphide) Corrective Action: High levels of organics in source water impacts treatment options and results in creation of higher than desirable levels of disinfection byproducts (THMs and HAAs). |